Vulnerabilities (CVE)

Filtered by vendor Schneider-electric Subscribe
Total 755 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2021-22793 1 Schneider-electric 5 Accusine Pcs\+, Accusine Pcsn, Accusine Pcsn Active Harmonic Filter Firmware and 2 more 2024-11-21 6.5 MEDIUM 7.2 HIGH
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exist in AccuSine PCS+ / PFV+ (Versions prior to V1.6.7) and AccuSine PCSn (Versions prior to V2.2.4) that could allow an authenticated attacker to access the device via FTP protocol.
CVE-2021-22792 1 Schneider-electric 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-476: NULL Pointer Dereference vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions).
CVE-2021-22791 1 Schneider-electric 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more 2024-11-21 4.0 MEDIUM 6.5 MEDIUM
A CWE-787: Out-of-bounds Write vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions).
CVE-2021-22790 1 Schneider-electric 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more 2024-11-21 4.0 MEDIUM 6.5 MEDIUM
A CWE-125: Out-of-bounds Read vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions).
CVE-2021-22789 1 Schneider-electric 49 Modicon M340 Bmxp341000, Modicon M340 Bmxp342010, Modicon M340 Bmxp342020 and 46 more 2024-11-21 4.0 MEDIUM 6.5 MEDIUM
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability that could cause a Denial of Service on the Modicon PLC controller / simulator when updating the controller application with a specially crafted project file exists in Modicon M580 CPU (part numbers BMEP* and BMEH*, all versions), Modicon M340 CPU (part numbers BMXP34*, all versions), Modicon MC80 (part numbers BMKC80*, all versions), Modicon Momentum Ethernet CPU (part numbers 171CBU*, all versions), PLC Simulator for EcoStruxureª Control Expert, including all Unity Pro versions (former name of EcoStruxureª Control Expert, all versions), PLC Simulator for EcoStruxureª Process Expert including all HDCS versions (former name of EcoStruxureª Process Expert, all versions), Modicon Quantum CPU (part numbers 140CPU*, all versions), Modicon Premium CPU (part numbers TSXP5*, all versions).
CVE-2021-22788 1 Schneider-electric 28 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 25 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-787: Out-of-bounds Write vulnerability exists that could cause denial of service when an attacker sends a specially crafted HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CVE-2021-22787 1 Schneider-electric 28 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 25 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-20: Improper Input Validation vulnerability exists that could cause denial of service of the device when an attacker sends a specially crafted HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CVE-2021-22785 1 Schneider-electric 28 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 25 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-200: Information Exposure vulnerability exists that could cause sensitive information of files located in the web root directory to leak when an attacker sends a HTTP request to the web server of the device. Affected Product: Modicon M340 CPUs: BMXP34 (Versions prior to V3.40), Modicon M340 X80 Ethernet Communication Modules: BMXNOE0100 (H), BMXNOE0110 (H), BMXNOC0401, BMXNOR0200H RTU (All Versions), Modicon Premium Processors with integrated Ethernet (Copro): TSXP574634, TSXP575634, TSXP576634 (All Versions), Modicon Quantum Processors with Integrated Ethernet (Copro): 140CPU65xxxxx (All Versions), Modicon Quantum Communication Modules: 140NOE771x1, 140NOC78x00, 140NOC77101 (All Versions), Modicon Premium Communication Modules: TSXETY4103, TSXETY5103 (All Versions)
CVE-2021-22784 1 Schneider-electric 1 C-bus Toolkit 2024-11-21 3.5 LOW 5.7 MEDIUM
A CWE-306: Missing Authentication for Critical Function vulnerability exists in C-Bus Toolkit v1.15.8 and prior that could allow an attacker to use a crafted webpage to obtain remote access to the system.
CVE-2021-22783 1 Schneider-electric 1 Ritto Wiser Door 2024-11-21 4.8 MEDIUM 8.8 HIGH
A CWE-200: Information Exposure vulnerability exists which could allow a session hijack when the door panel is communicating with the door. Affected Product: Ritto Wiser Door (All versions)
CVE-2021-22782 1 Schneider-electric 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect 2024-11-21 2.1 LOW 5.5 MEDIUM
Missing Encryption of Sensitive Data vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause an information leak allowing disclosure of network and process information, credentials or intellectual property when an attacker can access a project file.
CVE-2021-22781 1 Schneider-electric 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect 2024-11-21 2.1 LOW 5.5 MEDIUM
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause a leak of SMTP credential used for mailbox authentication when an attacker can access a project file.
CVE-2021-22780 1 Schneider-electric 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect 2024-11-21 3.6 LOW 7.1 HIGH
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause unauthorized access to a project file protected by a password when this file is shared with untrusted sources. An attacker may bypass the password protection and be able to view and modify a project file.
CVE-2021-22779 1 Schneider-electric 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more 2024-11-21 6.4 MEDIUM 9.1 CRITICAL
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
CVE-2021-22778 1 Schneider-electric 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect 2024-11-21 3.6 LOW 7.1 HIGH
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause protected derived function blocks to be read or modified by unauthorized users when accessing a project file.
CVE-2021-22777 1 Schneider-electric 1 Sosafe Configurable 2024-11-21 6.8 MEDIUM 7.8 HIGH
A CWE-502: Deserialization of Untrusted Data vulnerability exists that could cause code execution by opening a malicious project file.
CVE-2021-22775 1 Schneider-electric 1 Gp-pro Ex 2024-11-21 4.4 MEDIUM 7.8 HIGH
A CWE-427: Uncontrolled Search Path Element vulnerability exists in GP-Pro EX,V4.09.250 and prior, that could cause local code execution with elevated privileges when installing the software.
CVE-2021-22774 1 Schneider-electric 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A CWE-759: Use of a One-Way Hash without a Salt vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could lead an attacker to get knowledge of charging station user account credentials using dictionary attacks techniques.
CVE-2021-22773 1 Schneider-electric 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more 2024-11-21 4.0 MEDIUM 6.5 MEDIUM
A CWE-620: Unverified Password Change vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker connected to the charging station web server to modify the password of a user.
CVE-2021-22772 1 Schneider-electric 6 T200e, T200e Firmware, T200i and 3 more 2024-11-21 7.5 HIGH 9.8 CRITICAL
A CWE-306: Missing Authentication for Critical Function vulnerability exists in Easergy T200 ((Modbus) SC2-04MOD-07000100 and earlier), Easergy T200 ((IEC104) SC2-04IEC-07000100 and earlier), and Easergy T200 ((DNP3) SC2-04DNP-07000102 and earlier) that could cause unauthorized operation when authentication is bypassed.