Vulnerabilities (CVE)

Filtered by vendor Selinc Subscribe
Total 47 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2018-10608 1 Selinc 1 Acselerator Architect 2024-11-21 7.8 HIGH 7.5 HIGH
SEL AcSELerator Architect version 2.2.24.0 and prior can be exploited when the AcSELerator Architect FTP client connects to a malicious FTP server, which may cause denial of service via 100% CPU utilization. Restart of the application is required.
CVE-2018-10604 1 Selinc 1 Sel Compass 2024-11-21 6.5 MEDIUM 8.8 HIGH
SEL Compass version 3.0.5.1 and prior allows all users full access to the SEL Compass directory, which may allow modification or overwriting of files within the Compass installation folder, resulting in escalation of privilege and/or malicious code execution.
CVE-2018-10600 1 Selinc 1 Acselerator Architect 2024-11-21 7.5 HIGH 9.8 CRITICAL
SEL AcSELerator Architect version 2.2.24.0 and prior allows unsanitized input to be passed to the XML parser, which may allow disclosure and retrieval of arbitrary data, arbitrary code execution (in certain situations on specific platforms), and denial of service attacks.
CVE-2017-7928 1 Selinc 4 Sel-3620, Sel-3620 Firmware, Sel-3622 and 1 more 2024-11-21 7.5 HIGH 10.0 CRITICAL
An Improper Access Control issue was discovered in Schweitzer Engineering Laboratories (SEL) SEL-3620 and SEL-3622 Security Gateway Versions R202 and, R203, R203-V1, R203-V2 and, R204, R204-V1. The device does not properly enforce access control while configured for NAT port forwarding, which may allow for unauthorized communications to downstream devices.
CVE-2013-2798 1 Selinc 4 Sel-2241, Sel-3505, Sel-3530 and 1 more 2024-11-21 4.7 MEDIUM N/A
Schweitzer Engineering Laboratories (SEL) SEL-2241, SEL-3505, and SEL-3530 RTAC master devices allow physically proximate attackers to cause a denial of service (infinite loop) via crafted input over a serial line.
CVE-2013-2792 1 Selinc 4 Sel-2241, Sel-3505, Sel-3530 and 1 more 2024-11-21 7.1 HIGH N/A
Schweitzer Engineering Laboratories (SEL) SEL-2241, SEL-3505, and SEL-3530 RTAC master devices allow remote attackers to cause a denial of service (infinite loop) via a crafted DNP3 TCP packet.
CVE-2013-0665 1 Selinc 1 Acselerator Quickset 2024-11-21 6.2 MEDIUM N/A
Schweitzer Engineering Laboratories (SEL) AcSELerator QuickSet before 5.12.0.1 uses weak permissions for its Program Files directory, which allows local users to replace executable files, and consequently gain privileges, via standard filesystem operations.
CVE-2023-34388 1 Selinc 2 Sel-451, Sel-451 Firmware 2024-02-28 N/A 9.8 CRITICAL
An Improper Authentication vulnerability in the Schweitzer Engineering Laboratories SEL-451 could allow a remote unauthenticated attacker to potentially perform session hijacking attack and bypass authentication. See product Instruction Manual Appendix A dated 20230830 for more details.
CVE-2023-34390 1 Selinc 2 Sel-451, Sel-451 Firmware 2024-02-28 N/A 6.5 MEDIUM
An input validation vulnerability in the Schweitzer Engineering Laboratories SEL-451 could allow a remote authenticated attacker to create a denial of service against the system and locking out services. See product Instruction Manual Appendix A dated 20230830 for more details.
CVE-2023-34389 1 Selinc 2 Sel-451, Sel-451 Firmware 2024-02-28 N/A 6.5 MEDIUM
An allocation of resources without limits or throttling vulnerability in the Schweitzer Engineering Laboratories SEL-451 could allow a remote authenticated attacker to make the system unavailable for an indefinite amount of time. See product Instruction Manual Appendix A dated 20230830 for more details.
CVE-2023-2267 1 Selinc 2 Sel-411l, Sel-411l Firmware 2024-02-28 N/A 5.4 MEDIUM
An Improper Input Validation vulnerability in Schweitzer Engineering Laboratories SEL-411L could allow an attacker to perform reflection attacks against an authorized and authenticated user. See product Instruction Manual Appendix A dated 20230830 for more details.
CVE-2023-2264 1 Selinc 2 Sel-411l, Sel-411l Firmware 2024-02-28 N/A 7.8 HIGH
An improper input validation vulnerability in the Schweitzer Engineering Laboratories SEL-411L could allow a malicious actor to manipulate authorized users to click on a link that could allow undesired behavior. See product Instruction Manual Appendix A dated 20230830 for more details.
CVE-2023-2266 1 Selinc 2 Sel-411l, Sel-411l Firmware 2024-02-28 N/A 6.1 MEDIUM
An Improper neutralization of input during web page generation in the Schweitzer Engineering Laboratories SEL-411L could allow an attacker to generate cross-site scripting based attacks against an authorized and authenticated user. See product Instruction Manual Appendix A dated 20230830 for more details.
CVE-2023-31177 1 Selinc 2 Sel-451, Sel-451 Firmware 2024-02-28 N/A 6.1 MEDIUM
An Improper Neutralization of Input During Web Page Generation  ('Cross-site Scripting') in the Schweitzer Engineering Laboratories SEL-451 could allow an attacker to craft a link that could execute arbitrary code on a victim's system. See product Instruction Manual Appendix A dated 20230830 for more details.
CVE-2023-31176 1 Selinc 2 Sel-451, Sel-451 Firmware 2024-02-28 N/A 9.8 CRITICAL
An Insufficient Entropy vulnerability in the Schweitzer Engineering Laboratories SEL-451 could allow an unauthenticated remote attacker to brute-force session tokens and bypass authentication.  See product Instruction Manual Appendix A dated 20230830 for more details.
CVE-2023-2265 1 Selinc 2 Sel-411l, Sel-411l Firmware 2024-02-28 N/A 6.1 MEDIUM
An Improper Restriction of Rendered UI Layers or Frames in the Schweitzer Engineering Laboratories SEL-411L could allow an unauthenticated attacker to perform clickjacking based attacks against an authenticated and authorized user. See product Instruction Manual Appendix A dated 20230830 for more details.
CVE-2023-31175 1 Selinc 1 Sel-5037 Sel Grid Configurator 2024-02-28 N/A 9.8 CRITICAL
An Execution with Unnecessary Privileges vulnerability in the Schweitzer Engineering Laboratories SEL-5037 SEL Grid Configurator could allow an attacker to run system commands with the highest level privilege on the system. See Instruction Manual Appendix A and Appendix E dated 20230615 for more details. This issue affects SEL-5037 SEL Grid Configurator: before 4.5.0.20.
CVE-2023-31168 1 Selinc 1 Sel-5030 Acselerator Quickset 2024-02-28 N/A 6.5 MEDIUM
An Inclusion of Functionality from Untrusted Control Sphere vulnerability in the Schweitzer Engineering Laboratories SEL-5030 acSELerator QuickSet Software could allow an attacker to embed instructions that could be executed by an authorized device operator. See Instruction Manual Appendix A and Appendix E dated 20230615 for more details. This issue affects SEL-5030 acSELerator QuickSet Software: through 7.1.3.0.
CVE-2023-31171 1 Selinc 1 Sel-5030 Acselerator Quickset 2024-02-28 N/A 6.5 MEDIUM
An Improper Neutralization of Special Elements used in an SQL Command ('SQL Injection') vulnerability in the Schweitzer Engineering Laboratories SEL-5030 acSELerator QuickSet Software could allow an attacker to embed instructions that could be executed by an authorized device operator. See Instruction Manual Appendix A and Appendix E dated 20230615 for more details. This issue affects SEL-5030 acSELerator QuickSet Software: through 7.1.3.0.
CVE-2023-31167 2 Microsoft, Selinc 2 Windows, Sel-5036 Acselerator Bay Screen Builder 2024-02-28 N/A 8.1 HIGH
Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability in Schweitzer Engineering Laboratories SEL-5036 acSELerator Bay Screen Builder Software on Windows allows Relative Path Traversal. SEL acSELerator Bay Screen Builder software is distributed by SEL-5033 SEL acSELerator RTAC, SEL-5030 Quickset, and SEL Compass. CVE-2023-31167 and was patched in the acSELerator Bay Screen Builder release available on 20230602. Please contact SEL for additional details. This issue affects SEL-5036 acSELerator Bay Screen Builder Software: before 1.0.49152.778.