Total
7 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2022-26507 | 2 Att, Schneider-electric | 9 Xmill, Ecostruxure Control Expert, Ecostruxure Process Expert and 6 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
A heap-based buffer overflow exists in XML Decompression DecodeTreeBlock in AT&T Labs Xmill 0.7. A crafted input file can lead to remote code execution. This is not the same as any of: CVE-2021-21810, CVE-2021-21811, CVE-2021-21812, CVE-2021-21815, CVE-2021-21825, CVE-2021-21826, CVE-2021-21828, CVE-2021-21829, or CVE-2021-21830. NOTE: This vulnerability only affects products that are no longer supported by the maintainer | |||||
CVE-2021-22797 | 1 Schneider-electric | 8 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect and 5 more | 2024-11-21 | 9.3 HIGH | 7.8 HIGH |
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal) vulnerability exists that could cause malicious script to be deployed in an unauthorized location and may result in code execution on the engineering workstation when a malicious project file is loaded in the engineering software. Affected Product: EcoStruxure Control Expert (V15.0 SP1 and prior, including former Unity Pro), EcoStruxure Process Expert (2020 and prior, including former HDCS), SCADAPack RemoteConnect for x70 (All versions) | |||||
CVE-2021-22782 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2024-11-21 | 2.1 LOW | 5.5 MEDIUM |
Missing Encryption of Sensitive Data vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause an information leak allowing disclosure of network and process information, credentials or intellectual property when an attacker can access a project file. | |||||
CVE-2021-22781 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2024-11-21 | 2.1 LOW | 5.5 MEDIUM |
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause a leak of SMTP credential used for mailbox authentication when an attacker can access a project file. | |||||
CVE-2021-22780 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2024-11-21 | 3.6 LOW | 7.1 HIGH |
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause unauthorized access to a project file protected by a password when this file is shared with untrusted sources. An attacker may bypass the password protection and be able to view and modify a project file. | |||||
CVE-2021-22779 | 1 Schneider-electric | 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more | 2024-11-21 | 6.4 MEDIUM | 9.1 CRITICAL |
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller. | |||||
CVE-2021-22778 | 1 Schneider-electric | 3 Ecostruxure Control Expert, Ecostruxure Process Expert, Remoteconnect | 2024-11-21 | 3.6 LOW | 7.1 HIGH |
Insufficiently Protected Credentials vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), and SCADAPack RemoteConnect for x70, all versions, that could cause protected derived function blocks to be read or modified by unauthorized users when accessing a project file. |