Vulnerabilities (CVE)

Filtered by vendor Schneider-electric Subscribe
Filtered by product Modicon M580 Bmep585040 Firmware
Total 11 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2020-7543 1 Schneider-electric 32 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 29 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
CVE-2020-7542 1 Schneider-electric 40 140cpu65150, 140cpu65150 Firmware, Modicon M340 Bmxp341000 and 37 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
CVE-2020-7537 1 Schneider-electric 38 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 35 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
CVE-2022-37301 1 Schneider-electric 96 Modicon M340 Bmx P34-2010, Modicon M340 Bmx P34-2010 Firmware, Modicon M340 Bmx P34-2030 and 93 more 2024-02-28 N/A 7.5 HIGH
A CWE-191: Integer Underflow (Wrap or Wraparound) vulnerability exists that could cause a denial of service of the controller due to memory access violations when using the Modbus TCP protocol. Affected products: Modicon M340 CPU (part numbers BMXP34*)(V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*)(V3.22 and prior), Legacy Modicon Quantum/Premium(All Versions), Modicon Momentum MDI (171CBU*)(All Versions), Modicon MC80 (BMKC80)(V1.7 and prior)
CVE-2022-45788 1 Schneider-electric 108 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 105 more 2024-02-28 N/A 9.8 CRITICAL
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions)
CVE-2022-45789 1 Schneider-electric 72 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 69 more 2024-02-28 N/A 9.8 CRITICAL
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions)
CVE-2021-22786 1 Schneider-electric 82 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 79 more 2024-02-28 N/A 7.5 HIGH
A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum MDI (171CBU*) (Versions prior to V2.3), Legacy Modicon Quantum (All Versions)
CVE-2022-37300 1 Schneider-electric 70 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 67 more 2024-02-28 N/A 9.8 CRITICAL
A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior).
CVE-2021-22779 1 Schneider-electric 61 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 58 more 2024-02-28 6.4 MEDIUM 9.1 CRITICAL
Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.
CVE-2019-6855 1 Schneider-electric 44 Ecostruxure Control Expert, Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware and 41 more 2024-02-28 7.5 HIGH 7.3 HIGH
Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.
CVE-2018-7838 1 Schneider-electric 36 Bmeh582040, Bmeh582040 Firmware, Bmeh582040c and 33 more 2024-02-28 7.8 HIGH 7.5 HIGH
A CWE-119 Buffer Errors vulnerability exists in Modicon M580 CPU - BMEP582040, all versions before V2.90, and Modicon Ethernet Module BMENOC0301, all versions before V2.16, which could cause denial of service on the FTP service of the controller or the Ethernet BMENOC module when it receives a FTP CWD command with a data length greater than 1020 bytes. A power cycle is then needed to reactivate the FTP service.