Vulnerabilities (CVE)

Filtered by vendor Schneider-electric Subscribe
Filtered by product Modicon M340 Bmxp3420102cl
Total 18 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2018-7851 1 Schneider-electric 41 140cra312xxx, 140cra312xxx Firmware, Bmeh582040 and 38 more 2024-04-10 6.8 MEDIUM 6.5 MEDIUM
CWE-119: Buffer errors vulnerability exists in Modicon M580 with firmware prior to V2.50, Modicon M340 with firmware prior to V3.01, BMxCRA312xx with firmware prior to V2.40, All firmware versions of Modicon Premium and 140CRA312xxx when sending a specially crafted Modbus packet, which could cause a denial of service to the device that would force a restart to restore availability.
CVE-2019-6819 1 Schneider-electric 38 Bmeh582040, Bmeh582040c, Bmeh584040 and 35 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists which could cause a possible Denial of Service when specific Modbus frames are sent to the controller in the products: Modicon M340 - firmware versions prior to V3.01, Modicon M580 - firmware versions prior to V2.80, All firmware versions of Modicon Quantum and Modicon Premium.
CVE-2017-6017 1 Schneider-electric 30 Bmxnoc0401, Bmxnoc0401 Firmware, Bmxnoe0100 and 27 more 2024-04-10 7.8 HIGH 7.5 HIGH
A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.
CVE-2018-7761 1 Schneider-electric 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more 2024-04-10 7.5 HIGH 9.8 CRITICAL
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution.
CVE-2020-7543 1 Schneider-electric 32 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 29 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
CVE-2020-7542 1 Schneider-electric 40 140cpu65150, 140cpu65150 Firmware, Modicon M340 Bmxp341000 and 37 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
CVE-2020-7549 1 Schneider-electric 38 140cpu65150, 140cpu65150 Firmware, 140noc78000 and 35 more 2024-04-10 5.0 MEDIUM 5.3 MEDIUM
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause denial of HTTP and FTP services when a series of specially crafted requests is sent to the controller over HTTP.
CVE-2018-7760 1 Schneider-electric 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more 2024-04-10 7.5 HIGH 9.8 CRITICAL
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization.
CVE-2018-7759 1 Schneider-electric 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied.
CVE-2020-7536 1 Schneider-electric 20 Bmxnoe0100, Bmxnoe0100 Firmware, Bmxnoe0110 and 17 more 2024-04-10 7.8 HIGH 7.5 HIGH
A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP.
CVE-2018-7242 1 Schneider-electric 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more 2024-04-10 5.0 MEDIUM 9.8 CRITICAL
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks.
CVE-2020-7539 1 Schneider-electric 40 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 37 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause a denial of service vulnerability when a specially crafted packet is sent to the controller over HTTP.
CVE-2018-7762 1 Schneider-electric 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow.
CVE-2020-7541 1 Schneider-electric 40 140cpu65150, 140cpu65150 Firmware, 140noc77101 and 37 more 2024-04-10 5.0 MEDIUM 5.3 MEDIUM
A CWE-425: Direct Request ('Forced Browsing') vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of sensitive data when sending a specially crafted request to the controller over HTTP.
CVE-2020-7540 1 Schneider-electric 46 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 43 more 2024-04-10 7.5 HIGH 9.8 CRITICAL
A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests.
CVE-2020-7537 1 Schneider-electric 38 Modicon M340 Bmxp341000, Modicon M340 Bmxp341000 Firmware, Modicon M340 Bmxp342000 and 35 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.
CVE-2020-7535 1 Schneider-electric 42 140cpu65150, 140cpu65150 Firmware, 140cpu65160 and 39 more 2024-04-10 5.0 MEDIUM 7.5 HIGH
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.
CVE-2018-7241 1 Schneider-electric 114 140cpu31110, 140cpu31110 Firmware, 140cpu31110c and 111 more 2024-04-10 10.0 HIGH 9.8 CRITICAL
Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules.