Vulnerabilities (CVE)

Filtered by vendor Siemens Subscribe
Total 1848 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2022-32262 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 7.5 HIGH 9.8 CRITICAL
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). The affected application contains a file upload server that is vulnerable to command injection. An attacker could use this to achieve arbitrary code execution.
CVE-2022-32261 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). The affected application contains a misconfiguration in the APT update. This could allow an attacker to add insecure packages to the application.
CVE-2022-32260 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 7.5 HIGH 9.8 CRITICAL
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.2 SP1). The affected application creates temporary user credentials for UMC (User Management Component) users. An attacker could use these temporary credentials for authentication bypass in certain scenarios.
CVE-2022-32259 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 6.4 MEDIUM 6.5 MEDIUM
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). The system images for installation or update of the affected application contain unit test scripts with sensitive information. An attacker could gain information about testing architecture and also tamper with test configuration.
CVE-2022-32258 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). The affected application contains an older feature that allows to import device configurations via a specific endpoint. An attacker could use this vulnerability for information disclosure.
CVE-2022-32256 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 4.0 MEDIUM 6.5 MEDIUM
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). The affected application consists of a web service that lacks proper access control for some of the endpoints. This could lead to low privileged users accessing privileged information.
CVE-2022-32255 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 5.0 MEDIUM 5.3 MEDIUM
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). The affected application consists of a web service that lacks proper access control for some of the endpoints. This could lead to unauthorized access to limited information.
CVE-2022-32254 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). A customized HTTP POST request could force the application to write the status of a given user to a log file, exposing sensitive user information that could provide valuable guidance to an attacker.
CVE-2022-32253 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). Due to improper input validation, the OpenSSL certificate's password could be printed to a file reachable by an attacker.
CVE-2022-32252 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 9.3 HIGH 7.8 HIGH
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). The application does not perform the integrity check of the update packages. Without validation, an admin user might be tricked to install a malicious package, granting root privileges to an attacker.
CVE-2022-32251 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 7.5 HIGH 9.8 CRITICAL
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). There is a missing authentication verification for a resource used to change the roles and permissions of a user. This could allow an attacker to change the permissions of any user and gain the privileges of an administrative user.
CVE-2022-30527 1 Siemens 1 Sinec Nms 2024-07-09 N/A 7.8 HIGH
A vulnerability has been identified in SINEC NMS (All versions < V2.0). The affected application assigns improper access rights to specific folders containing executable files and libraries. This could allow an authenticated local attacker to inject arbitrary code and escalate privileges.
CVE-2022-29034 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 4.3 MEDIUM 6.1 MEDIUM
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). An error message pop up window in the web interface of the affected application does not prevent injection of JavaScript code. This could allow attackers to perform reflected cross-site scripting (XSS) attacks.
CVE-2022-27221 1 Siemens 1 Sinema Remote Connect Server 2024-07-09 4.3 MEDIUM 5.9 MEDIUM
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V3.1). An attacker in machine-in-the-middle could obtain plaintext secret values by observing length differences during a series of guesses in which a string in an HTTP request URL potentially matches an unknown string in an HTTP response body, aka a "BREACH" attack.
CVE-2022-25622 1 Siemens 23 Simatic Cfu Diq, Simatic Cfu Diq Firmware, Simatic Cfu Pa and 20 more 2024-07-09 5.0 MEDIUM 7.5 HIGH
The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP-Header length is less than defined. This could allow an attacker to create a denial of service condition for TCP services on affected devices by sending specially crafted TCP segments.
CVE-2019-19300 1 Siemens 65 Ktk Ate530s, Ktk Ate530s Firmware, Sidoor Atd430w and 62 more 2024-07-09 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, KTK ATE530S, SIDOOR ATD430W, SIDOOR ATE530S COATED, SIDOOR ATE531S, SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0), SIMATIC ET 200pro IM 154-8 PN/DP CPU (6ES7154-8AB01-0AB0), SIMATIC ET 200pro IM 154-8F PN/DP CPU (6ES7154-8FB01-0AB0), SIMATIC ET 200pro IM 154-8FX PN/DP CPU (6ES7154-8FX00-0AB0), SIMATIC ET 200S IM 151-8 PN/DP CPU (6ES7151-8AB01-0AB0), SIMATIC ET 200S IM 151-8F PN/DP CPU (6ES7151-8FB01-0AB0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants), SIMATIC ET 200SP IM 155-6 PN HF (6ES7155-6AU00-0CN0), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants), SIMATIC ET200ecoPN, AI 8xRTD/TC, M12-L (6ES7144-6JF00-0BB0), SIMATIC ET200ecoPN, CM 4x IO-Link, M12-L (6ES7148-6JE00-0BB0), SIMATIC ET200ecoPN, CM 8x IO-Link, M12-L (6ES7148-6JG00-0BB0), SIMATIC ET200ecoPN, CM 8x IO-Link, M12-L (6ES7148-6JJ00-0BB0), SIMATIC ET200ecoPN, DI 16x24VDC, M12-L (6ES7141-6BH00-0BB0), SIMATIC ET200ecoPN, DI 8x24VDC, M12-L (6ES7141-6BG00-0BB0), SIMATIC ET200ecoPN, DIQ 16x24VDC/2A, M12-L (6ES7143-6BH00-0BB0), SIMATIC ET200ecoPN, DQ 8x24VDC/0,5A, M12-L (6ES7142-6BG00-0BB0), SIMATIC ET200ecoPN, DQ 8x24VDC/2A, M12-L (6ES7142-6BR00-0BB0), SIMATIC MICRO-DRIVE PDC, SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0), SIMATIC S7-1200 CPU family (incl. SIPLUS variants), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-1500 Software Controller, SIMATIC S7-300 CPU 314C-2 PN/DP (6ES7314-6EH04-0AB0), SIMATIC S7-300 CPU 315-2 PN/DP (6ES7315-2EH14-0AB0), SIMATIC S7-300 CPU 315F-2 PN/DP (6ES7315-2FJ14-0AB0), SIMATIC S7-300 CPU 315T-3 PN/DP (6ES7315-7TJ10-0AB0), SIMATIC S7-300 CPU 317-2 PN/DP (6ES7317-2EK14-0AB0), SIMATIC S7-300 CPU 317F-2 PN/DP (6ES7317-2FK14-0AB0), SIMATIC S7-300 CPU 317T-3 PN/DP (6ES7317-7TK10-0AB0), SIMATIC S7-300 CPU 317TF-3 PN/DP (6ES7317-7UL10-0AB0), SIMATIC S7-300 CPU 319-3 PN/DP (6ES7318-3EL01-0AB0), SIMATIC S7-300 CPU 319F-3 PN/DP (6ES7318-3FL01-0AB0), SIMATIC S7-400 H V6 and below CPU family (incl. SIPLUS variants), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX 2010 (6ES7671-0RC08-0YA0), SIMATIC WinAC RTX F 2010 (6ES7671-1RC08-0YA0), SINAMICS S/G Control Unit w. PROFINET, SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0), SIPLUS ET 200S IM 151-8 PN/DP CPU (6AG1151-8AB01-7AB0), SIPLUS ET 200S IM 151-8F PN/DP CPU (6AG1151-8FB01-2AB0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-2CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU00-4CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU00-1CN0), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0), SIPLUS S7-300 CPU 314C-2 PN/DP (6AG1314-6EH04-7AB0), SIPLUS S7-300 CPU 315-2 PN/DP (6AG1315-2EH14-7AB0), SIPLUS S7-300 CPU 315F-2 PN/DP (6AG1315-2FJ14-2AB0), SIPLUS S7-300 CPU 317-2 PN/DP (6AG1317-2EK14-7AB0), SIPLUS S7-300 CPU 317F-2 PN/DP (6AG1317-2FK14-2AB0). The Interniche-based TCP Stack can be forced to make very expensive calls for every incoming packet which can lead to a denial of service.
CVE-2019-13946 1 Siemens 101 Dk Standard Ethernet Controller, Ek-ertec 200, Ek-ertec 200 Firmware and 98 more 2024-07-09 7.8 HIGH 7.5 HIGH
Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit internal resource allocation when multiple legitimate diagnostic package requests are sent to the DCE-RPC interface. This could lead to a denial of service condition due to lack of memory for devices that include a vulnerable version of the stack. The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device.
CVE-2019-10936 1 Siemens 130 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 and 127 more 2024-07-09 5.0 MEDIUM 7.5 HIGH
Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a denial of service condition.
CVE-2017-12741 1 Siemens 76 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200p and 73 more 2024-07-09 7.8 HIGH 7.5 HIGH
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.
CVE-2023-33919 1 Siemens 3 Cp-8031 Master Module, Cp-8050 Master Module, Cpci85 Firmware 2024-07-04 N/A 7.2 HIGH
A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05), CP-8050 MASTER MODULE (All versions < CPCI85 V05). The web interface of affected devices is vulnerable to command injection due to missing server side input sanitation. This could allow an authenticated privileged remote attacker to execute arbitrary code with root privileges.