CVE-2019-10918 1 Siemens 4 Simatic Pcs 7, Simatic Wincc, Simatic Wincc \(tia Portal\) and 1 more 2024-02-28 9.0 HIGH 8.8 HIGH
A vulnerability has been identified in SIMATIC PCS 7 V8.0 and earlier (All versions), SIMATIC PCS 7 V8.1 (All versions < V8.1 with WinCC V7.3 Upd 19), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1 with WinCC V7.4 SP1 Upd11), SIMATIC PCS 7 V9.0 (All versions < V9.0 SP2 with WinCC V7.4 SP1 Upd11), SIMATIC WinCC (TIA Portal) V13 (All versions), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1 Upd 9), SIMATIC WinCC (TIA Portal) V15 (All versions < V15.1 Upd 3), SIMATIC WinCC Runtime Professional V13 (All versions), SIMATIC WinCC Runtime Professional V14 (All versions < V14.1 Upd 8), SIMATIC WinCC Runtime Professional V15 (All versions < V15.1 Upd 3), SIMATIC WinCC V7.2 and earlier (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Upd 19), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd 11), SIMATIC WinCC V7.5 (All versions < V7.5 Upd 3). An authenticatd attacker with network access to the DCOM interface could execute arbitrary commands with SYSTEM privileges. The vulnerability could be exploited by an attacker with network access to the affected system. Successful exploitation requires authentication with a low-privileged user account and no user interaction. An attacker could use the vulnerability to compromise confidentiality and integrity and availability of the affected system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2018-13808 1 Siemens 4 Cp 1604, Cp 1604 Firmware, Cp 1616 and 1 more 2024-02-28 6.4 MEDIUM 9.1 CRITICAL
A vulnerability has been identified in CP 1604 (All versions), CP 1616 (All versions). An attacker with network access to port 23/tcp could extract internal communication data or cause a Denial-of-Service condition. Successful exploitation requires network access to a vulnerable device. At the time of advisory publication no public exploitation of this vulnerability was known.
CVE-2018-7082 2 Arubanetworks, Siemens 3 Aruba Instant, Scalance W1750d, Scalance W1750d Firmware 2024-02-28 9.0 HIGH 7.2 HIGH
A command injection vulnerability is present in Aruba Instant that permits an authenticated administrative user to execute arbitrary commands on the underlying operating system. A malicious administrator could use this ability to install backdoors or change system configuration in a way that would not be logged. Workaround: None. Resolution: Fixed in Aruba Instant 4.2.4.12, 6.5.4.11, 8.3.0.6, and 8.4.0.0
CVE-2019-8273 2 Siemens, Uvnc 4 Sinumerik Access Mymachine\/p2p, Sinumerik Pcu Base Win10 Software\/ipc, Sinumerik Pcu Base Win7 Software\/ipc and 1 more 2024-02-28 7.5 HIGH 9.8 CRITICAL
UltraVNC revision 1211 has a heap buffer overflow vulnerability in VNC server code inside file transfer request handler, which can potentially result in code execution. This attack appears to be exploitable via network connectivity. This vulnerability has been fixed in revision 1212.
CVE-2019-10933 1 Siemens 4 Spectrum Power 3, Spectrum Power 4, Spectrum Power 5 and 1 more 2024-02-28 4.3 MEDIUM 6.1 MEDIUM
A vulnerability has been identified in Spectrum Power 3 (Corporate User Interface) (All versions <= v3.11), Spectrum Power 4 (Corporate User Interface) (Version v4.75), Spectrum Power 5 (Corporate User Interface) (All versions < v5.50), Spectrum Power 7 (Corporate User Interface) (All versions <= v2.20). The web server could allow Cross-Site Scripting (XSS) attacks if unsuspecting users are tricked into accessing a malicious link. User interaction is required for a successful exploitation. The user does not need to be logged into the web interface in order for the exploitation to succeed.At the stage of publishing this security advisory no public exploitation is known.
CVE-2019-13920 1 Siemens 1 Sinema Remote Connect Server 2024-02-28 4.3 MEDIUM 4.3 MEDIUM
A vulnerability has been identified in SINEMA Remote Connect Server (All versions < V2.0 SP1). Some parts of the web application are not protected against Cross Site Request Forgery (CSRF) attacks. The security vulnerability could be exploited by an attacker that is able to trigger requests of a logged-in user to the application. The vulnerability could allow switching the connectivity state of a user or a device. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2018-11466 1 Siemens 10 Sinumerik 808d V4.7, Sinumerik 808d V4.7 Firmware, Sinumerik 808d V4.8 and 7 more 2024-02-28 7.5 HIGH 9.8 CRITICAL
A vulnerability has been identified in SINUMERIK 808D V4.7 (All versions), SINUMERIK 808D V4.8 (All versions), SINUMERIK 828D V4.7 (All versions < V4.7 SP6 HF1), SINUMERIK 840D sl V4.7 (All versions < V4.7 SP6 HF5), SINUMERIK 840D sl V4.8 (All versions < V4.8 SP3). Specially crafted network packets sent to port 102/tcp (ISO-TSAP) could allow a remote attacker to either cause a Denial-of-Service condition of the integrated software firewall or allow to execute code in the context of the software firewall. The security vulnerability could be exploited by an attacker with network access to the affected systems on port 102/tcp. Successful exploitation requires no user privileges and no user interaction. The vulnerability could allow an attacker to compromise confidentiality, integrity and availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known
CVE-2018-15473 7 Canonical, Debian, Netapp and 4 more 24 Ubuntu Linux, Debian Linux, Aff Baseboard Management Controller and 21 more 2024-02-28 5.0 MEDIUM 5.3 MEDIUM
OpenSSH through 7.7 is prone to a user enumeration vulnerability due to not delaying bailout for an invalid authenticating user until after the packet containing the request has been fully parsed, related to auth2-gss.c, auth2-hostbased.c, and auth2-pubkey.c.
CVE-2018-11451 1 Siemens 33 6md85, 6md86, 7ke85 and 30 more 2024-02-28 7.8 HIGH 7.5 HIGH
A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.33), Firmware variant PROFINET IO for EN100 Ethernet module (All versions), Firmware variant Modbus TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions < V1.22), SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions < V7.80), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.58). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the affected products. A manual restart is required to recover the EN100 module functionality of the affected devices. Successful exploitation requires an attacker with network access to send multiple packets to the affected products or modules. As a precondition the IEC 61850-MMS communication needs to be activated on the affected products or modules. No user interaction or privileges are required to exploit the vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the network functionality of the device, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2018-13813 1 Siemens 22 Simatic Hmi Comfort Outdoor Panels, Simatic Hmi Comfort Outdoor Panels Firmware, Simatic Hmi Comfort Panels and 19 more 2024-02-28 5.8 MEDIUM 8.1 HIGH
A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15 Update 4), SIMATIC WinCC Runtime Advanced (All versions < V15 Update 4), SIMATIC WinCC Runtime Professional (All versions < V15 Update 4), SIMATIC WinCC (TIA Portal) (All versions < V15 Update 4), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). The webserver of affected HMI devices may allow URL redirections to untrusted websites. An attacker must trick a valid user who is authenticated to the device into clicking on a malicious link to exploit the vulnerability. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2018-16557 1 Siemens 8 Simatic S7-400, Simatic S7-400 Firmware, Simatic S7-400 Pn\/dp V7 and 5 more 2024-02-28 7.8 HIGH 8.2 HIGH
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
CVE-2018-11454 1 Siemens 2 Simatic Step 7 \(tia Portal\), Simatic Wincc \(tia Portal\) 2024-02-28 4.4 MEDIUM 8.6 HIGH
A vulnerability has been identified in SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V10, V11, V12 (All versions), SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V13 (All versions < V13 SP2 Update 2), SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V14 (All versions < V14 SP1 Update 6), SIMATIC STEP 7 (TIA Portal) and WinCC (TIA Portal) V15 (All versions < V15 Update 2). Improper file permissions in the default installation of TIA Portal may allow an attacker with local file system access to manipulate resources which may be transferred to devices and executed there by a different user. No special privileges are required, but the victim needs to transfer the manipulated files to a device. Execution is caused on the target device rather than on the PG device.
CVE-2018-20749 4 Canonical, Debian, Libvnc Project and 1 more 15 Ubuntu Linux, Debian Linux, Libvncserver and 12 more 2024-02-28 7.5 HIGH 9.8 CRITICAL
LibVNC before 0.9.12 contains a heap out-of-bounds write vulnerability in libvncserver/rfbserver.c. The fix for CVE-2018-15127 was incomplete.
CVE-2018-16556 1 Siemens 10 Simatic S7-400, Simatic S7-400 Firmware, Simatic S7-400 Pn\/dp V7 and 7 more 2024-02-28 7.8 HIGH 7.5 HIGH
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
CVE-2018-11455 1 Siemens 1 Automation License Manager 2024-02-28 6.8 MEDIUM 8.8 HIGH
A vulnerability has been identified in Automation License Manager 5 (All versions < 5.3.4.4), Automation License Manager 6 (All versions < 6.0.1). A directory traversal vulnerability could allow a remote attacker to move arbitrary files, which can result in code execution, compromising confidentiality, integrity and availability of the system. Successful exploitation requires a network connection to the affected device. The attacker does not need privileges or special conditions of the system, but user interaction is required.
CVE-2018-11463 1 Siemens 10 Sinumerik 808d V4.7, Sinumerik 808d V4.7 Firmware, Sinumerik 808d V4.8 and 7 more 2024-02-28 4.6 MEDIUM 7.8 HIGH
A vulnerability has been identified in SINUMERIK 808D V4.7 (All versions), SINUMERIK 808D V4.8 (All versions), SINUMERIK 828D V4.7 (All versions < V4.7 SP6 HF1), SINUMERIK 840D sl V4.7 (All versions < V4.7 SP6 HF5), SINUMERIK 840D sl V4.8 (All versions < V4.8 SP3). A buffer overflow in the service command application could allow a local attacker to execute code with elevated privileges. The security vulnerability could be exploited by an attacker with local access to the affected systems. Successful exploitation requires user privileges but no user interaction. The vulnerability could allow an attacker to compromise confidentiality, integrity and availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2018-13806 1 Siemens 1 Td Keypad Designer 2024-02-28 9.3 HIGH 7.8 HIGH
A vulnerability has been identified in SIEMENS TD Keypad Designer (All versions). A DLL hijacking vulnerability exists in all versions of SIEMENS TD Keypad Designer which could allow an attacker to execute code with the permission of the user running TD Designer. The attacker must have write access to the directory containing the TD project file in order to exploit the vulnerability. A legitimate user with higher privileges than the attacker must open the TD project in order for this vulnerability to be exploited. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2018-11462 1 Siemens 10 Sinumerik 808d V4.7, Sinumerik 808d V4.7 Firmware, Sinumerik 808d V4.8 and 7 more 2024-02-28 7.5 HIGH 9.8 CRITICAL
A vulnerability has been identified in SINUMERIK 808D V4.7 (All versions), SINUMERIK 808D V4.8 (All versions), SINUMERIK 828D V4.7 (All versions < V4.7 SP6 HF1), SINUMERIK 840D sl V4.7 (All versions < V4.7 SP6 HF5), SINUMERIK 840D sl V4.8 (All versions < V4.8 SP3). By sending a specially crafted authentication request to the affected systems a remote attacker could escalate his privileges to an elevated user account but not to root. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no privileges and no user interaction. The vulnerability could allow an attacker to compromise confidentiality, integrity and availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known.
CVE-2018-13815 1 Siemens 4 Simatic S7-1200, Simatic S7-1200 Firmware, Simatic S7-1500 and 1 more 2024-02-28 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a Denial-of-Service condition impacting the availability of the system. At the time of advisory publication no public exploitation of this vulnerability was known.
CVE-2018-13807 1 Siemens 6 Scalance X300, Scalance X300 Firmware, Scalance X408 and 3 more 2024-02-28 7.8 HIGH 8.6 HIGH
A vulnerability has been identified in SCALANCE X300 (All versions < V4.0.0), SCALANCE X408 (All versions < V4.0.0), SCALANCE X414 (All versions). The web interface on port 443/tcp could allow an attacker to cause a Denial-of-Service condition by sending specially crafted packets to the web server. The device will automatically reboot, impacting network availability for other devices. An attacker must have network access to port 443/tcp to exploit the vulnerability. Neither valid credentials nor interaction by a legitimate user is required to exploit the vulnerability. There is no confidentiality or integrity impact, only availability is temporarily impacted. This vulnerability could be triggered by publicly available tools.