Total
25 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2020-27737 | 1 Siemens | 6 Nucleus Net, Nucleus Readystart V3, Nucleus Readystart V4 and 3 more | 2024-11-21 | 5.8 MEDIUM | 6.5 MEDIUM |
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS response parsing functionality does not properly validate various length and counts of the records. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the memory past the allocated structure. | |||||
CVE-2020-27736 | 1 Siemens | 6 Nucleus Net, Nucleus Readystart V3, Nucleus Readystart V4 and 3 more | 2024-11-21 | 5.8 MEDIUM | 6.5 MEDIUM |
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory. | |||||
CVE-2020-27009 | 1 Siemens | 2 Nucleus Net, Nucleus Source Code | 2024-11-21 | 6.8 MEDIUM | 8.1 HIGH |
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus Source Code (Versions including affected DNS modules), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name record decompression functionality does not properly validate the pointer offset values. The parsing of malformed responses could result in a write past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to execute code in the context of the current process or cause a denial-of-service condition. | |||||
CVE-2020-15795 | 1 Siemens | 2 Nucleus Net, Nucleus Source Code | 2024-11-21 | 6.8 MEDIUM | 8.1 HIGH |
A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus Source Code (Versions including affected DNS modules), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the names in DNS-responses. The parsing of malformed responses could result in a write past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to execute code in the context of the current process or cause a denial-of-service condition. | |||||
CVE-2019-13939 | 1 Siemens | 46 Apogee Modular Building Controller, Apogee Modular Building Controller Firmware, Apogee Modular Equiment Controller and 43 more | 2024-11-21 | 4.8 MEDIUM | 7.1 HIGH |
A vulnerability has been identified in Capital Embedded AR Classic 431-422 (All versions), Capital Embedded AR Classic R20-11 (All versions < V2303), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus Source Code (All versions). By sending specially crafted DHCP packets to a device where the DHCP client is enabled, an attacker could change the IP address of the device to an invalid value. |