CVE-2020-27736

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory.
Configurations

Configuration 1 (hide)

OR cpe:2.3:a:siemens:nucleus_net:*:*:*:*:*:*:*:*
cpe:2.3:a:siemens:nucleus_readystart_v3:*:*:*:*:*:*:*:*
cpe:2.3:a:siemens:nucleus_readystart_v4:*:*:*:*:*:*:*:*
cpe:2.3:a:siemens:nucleus_source_code:-:*:*:*:*:*:*:*

Configuration 2 (hide)

AND
cpe:2.3:o:siemens:simotics_connect_400_firmware:*:*:*:*:*:*:*:*
cpe:2.3:h:siemens:simotics_connect_400:-:*:*:*:*:*:*:*

History

08 Aug 2023, 10:15

Type Values Removed Values Added
References
  • (MISC) https://cert-portal.siemens.com/productcert/pdf/ssa-180579.pdf -
Summary A vulnerability has been identified in Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory. A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions), Nucleus ReadyStart V3 (All versions < V2017.02.3), Nucleus ReadyStart V4 (All versions < V4.1.0), Nucleus Source Code (Versions including affected DNS modules), SIMOTICS CONNECT 400 (All versions < V0.5.0.0), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). The DNS domain name label parsing functionality does not properly validate the null-terminated name in DNS-responses. The parsing of malformed responses could result in a read past the end of an allocated structure. An attacker with a privileged position in the network could leverage this vulnerability to cause a denial-of-service condition or leak the read memory.

Information

Published : 2021-04-22 21:15

Updated : 2024-02-28 18:28


NVD link : CVE-2020-27736

Mitre link : CVE-2020-27736

CVE.ORG link : CVE-2020-27736


JSON object : View

Products Affected

siemens

  • nucleus_source_code
  • simotics_connect_400
  • nucleus_net
  • nucleus_readystart_v4
  • simotics_connect_400_firmware
  • nucleus_readystart_v3
CWE
CWE-125

Out-of-bounds Read

CWE-170

Improper Null Termination