CVE-2022-45792 1 Omron 1 Sysmac Studio 2024-11-21 N/A 7.8 HIGH
Project files may contain malicious contents which the software will use to create files on the filesystem. This allows directory traversal and overwriting files with the privileges of the logged-in user.
CVE-2022-34151 1 Omron 113 Na5-12w, Na5-12w Firmware, Na5-15w and 110 more 2024-11-21 6.8 MEDIUM 8.1 HIGH
Use of hard-coded credentials vulnerability exists in Machine automation controller NJ series all models V 1.48 and earlier, Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, Automation software 'Sysmac Studio' all models V1.49 and earlier, and Programmable Terminal (PT) NA series NA5-15W/NA5-12W/NA5-9W/NA5-7W models Runtime V1.15 and earlier, which may allow a remote attacker who successfully obtained the user credentials by analyzing the affected product to access the controller.
CVE-2022-33208 1 Omron 113 Na5-12w, Na5-12w Firmware, Na5-15w and 110 more 2024-11-21 6.8 MEDIUM 8.1 HIGH
Authentication bypass by capture-replay vulnerability exists in Machine automation controller NJ series all models V 1.48 and earlier, Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, Automation software 'Sysmac Studio' all models V1.49 and earlier, and Programmable Terminal (PT) NA series NA5-15W/NA5-12W/NA5-9W/NA5-7W models Runtime V1.15 and earlier, which may allow a remote attacker who can analyze the communication between the affected controller and automation software 'Sysmac Studio' and/or a Programmable Terminal (PT) to access the controller.