Vulnerabilities (CVE)

Filtered by vendor Omron Subscribe
Filtered by product Sysmac Cj2h
Total 3 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2022-31207 1 Omron 14 Cp1w-cif41, Cp1w-cif41 Firmware, Sysmac Cj2h and 11 more 2024-11-21 N/A 9.8 CRITICAL
The Omron SYSMAC Cx product family PLCs (CS series, CJ series, and CP series) through 2022-05-18 lack cryptographic authentication. They utilize the Omron FINS (9600/TCP) protocol for engineering purposes, including downloading projects and control logic to the PLC. This protocol has authentication flaws as reported in FSCT-2022-0057. Control logic is downloaded to PLC volatile memory using the FINS Program Area Read and Program Area Write commands or to non-volatile memory using other commands from where it can be loaded into volatile memory for execution. The logic that is loaded into and executed from the user program area exists in compiled object code form. Upon execution, these object codes are first passed to a dedicated ASIC that determines whether the object code is to be executed by the ASIC or the microprocessor. In the former case, the object code is interpreted by the ASIC whereas in the latter case the object code is passed to the microprocessor for object code interpretation by a ROM interpreter. In the abnormal case where the object code cannot be handled by either, an abnormal condition is triggered and the PLC is halted. The logic that is downloaded to the PLC does not seem to be cryptographically authenticated, thus allowing an attacker to manipulate transmitted object code to the PLC and either execute arbitrary object code commands on the ASIC or on the microprocessor interpreter.
CVE-2022-31205 1 Omron 14 Cp1w-cif41, Cp1w-cif41 Firmware, Sysmac Cj2h and 11 more 2024-11-21 N/A 7.5 HIGH
In Omron CS series, CJ series, and CP series PLCs through 2022-05-18, the password for access to the Web UI is stored in memory area D1449...D1452 and can be read out using the Omron FINS protocol without any further authentication.
CVE-2022-31204 1 Omron 15 Cp1w-cif41, Cp1w-cif41 Firmware, Cx-programmer and 12 more 2024-11-21 N/A 7.5 HIGH
Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.