CVE-2022-25622 1 Siemens 23 Simatic Cfu Diq, Simatic Cfu Diq Firmware, Simatic Cfu Pa and 20 more 2024-11-21 5.0 MEDIUM 5.3 MEDIUM
The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP-Header length is less than defined. This could allow an attacker to create a denial of service condition for TCP services on affected devices by sending specially crafted TCP segments.
CVE-2021-40368 1 Siemens 8 Simatic S7-400 Pn\/dp V7, Simatic S7-400 Pn\/dp V7 Firmware, Simatic S7-400h V6 and 5 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.10), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants) (All versions < V10.1), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions < V8.2.3), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Affected devices improperly handle specially crafted packets sent to port 102/tcp. This could allow an attacker to create a Denial-of-Service condition. A restart is needed to restore normal operations.
CVE-2019-10936 1 Siemens 130 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 and 127 more 2024-11-21 5.0 MEDIUM 7.5 HIGH
Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a denial of service condition.
CVE-2018-16556 1 Siemens 10 Simatic S7-400, Simatic S7-400 Firmware, Simatic S7-400 Pn\/dp V7 and 7 more 2024-11-21 7.8 HIGH 7.5 HIGH
A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.
CVE-2017-12741 1 Siemens 76 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200p and 73 more 2024-11-21 7.8 HIGH 7.5 HIGH
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.