Vulnerabilities (CVE)

Filtered by vendor Rockwellautomation Subscribe
Filtered by product Guardlogix 5580 Firmware
Total 7 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2024-6207 1 Rockwellautomation 16 Compact Guardlogix 5380 Sil 2, Compact Guardlogix 5380 Sil 2 Firmware, Compact Guardlogix 5380 Sil 3 and 13 more 2024-10-21 N/A 7.5 HIGH
CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html  and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running.
CVE-2024-6077 1 Rockwellautomation 14 1756-en4, 1756-en4 Firmware, Compact Guardlogix 5380 Sil 2 and 11 more 2024-09-19 N/A 7.5 HIGH
A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover.
CVE-2022-3752 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2024-02-28 N/A 7.5 HIGH
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.
CVE-2020-6998 1 Rockwellautomation 18 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compact Guardlogix 5370 and 15 more 2024-02-28 N/A 8.6 HIGH
The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products.
CVE-2022-1161 1 Rockwellautomation 48 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 45 more 2024-02-28 7.5 HIGH 9.8 CRITICAL
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
CVE-2022-1159 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2024-02-28 6.5 MEDIUM 7.2 HIGH
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user.
CVE-2022-1797 1 Rockwellautomation 18 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 15 more 2024-02-28 7.8 HIGH 8.6 HIGH
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.