Filtered by vendor Rockwellautomation
Subscribe
Filtered by product Controllogix 5580 Firmware
Subscribe
Total
6 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2024-6207 | 1 Rockwellautomation | 16 Compact Guardlogix 5380 Sil 2, Compact Guardlogix 5380 Sil 2 Firmware, Compact Guardlogix 5380 Sil 3 and 13 more | 2024-10-21 | N/A | 7.5 HIGH |
CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running. | |||||
CVE-2024-6077 | 1 Rockwellautomation | 14 1756-en4, 1756-en4 Firmware, Compact Guardlogix 5380 Sil 2 and 11 more | 2024-09-19 | N/A | 7.5 HIGH |
A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover. | |||||
CVE-2022-1161 | 1 Rockwellautomation | 48 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 45 more | 2024-02-28 | 7.5 HIGH | 9.8 CRITICAL |
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other. | |||||
CVE-2022-1159 | 1 Rockwellautomation | 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more | 2024-02-28 | 6.5 MEDIUM | 7.2 HIGH |
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user. | |||||
CVE-2022-1797 | 1 Rockwellautomation | 18 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 15 more | 2024-02-28 | 7.8 HIGH | 8.6 HIGH |
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online. | |||||
CVE-2017-6024 | 1 Rockwellautomation | 4 Compactlogix 5380, Compactlogix 5380 Firmware, Controllogix 5580 and 1 more | 2024-02-28 | 7.1 HIGH | 5.9 MEDIUM |
A Resource Exhaustion issue was discovered in Rockwell Automation ControlLogix 5580 controllers V28.011, V28.012, and V28.013; ControlLogix 5580 controllers V29.011; CompactLogix 5380 controllers V28.011; and CompactLogix 5380 controllers V29.011. This vulnerability may allow an attacker to cause a denial of service condition by sending a series of specific CIP-based commands to the controller. |