Total
25 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2023-26593 | 1 Yokogawa | 8 B\/m9000 Vp, B\/m9000cs, Centum Cs 1000 and 5 more | 2024-11-21 | N/A | 7.8 HIGH |
CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is installed tampers the password file stored in the computer, the user privilege which CENTUM managed may be escalated. As a result, the control system may be operated with the escalated user privilege. To exploit this vulnerability, the following prerequisites must be met: (1)An attacker has obtained user credentials where the affected product is installed, (2)CENTUM Authentication Mode is used for user authentication when CENTUM VP is used. The affected products and versions are as follows: CENTUM CS 1000, CENTUM CS 3000 (Including CENTUM CS 3000 Entry Class) R2.01.00 to R3.09.50, CENTUM VP (Including CENTUM VP Entry Class) R4.01.00 to R4.03.00, R5.01.00 to R5.04.20, and R6.01.00 and later, B/M9000 CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R7.04.51 and R8.01.01 and later | |||||
CVE-2022-30707 | 1 Yokogawa | 11 B\/m9000 Vp, B\/m9000cs, Centum Cs 3000 and 8 more | 2024-11-21 | 5.4 MEDIUM | 8.8 HIGH |
Violation of secure design principles exists in the communication of CAMS for HIS. Affected products and versions are CENTUM series where LHS4800 is installed (CENTUM CS 3000 and CENTUM CS 3000 Small R3.08.10 to R3.09.00), CENTUM series where CAMS function is used (CENTUM VP, CENTUM VP Small, and CENTUM VP Basic R4.01.00 to R4.03.00), CENTUM series regardless of the use of CAMS function (CENTUM VP, CENTUM VP Small, and CENTUM VP Basic R5.01.00 to R5.04.20 and R6.01.00 to R6.09.00), Exaopc R3.72.00 to R3.80.00 (only if NTPF100-S6 'For CENTUM VP Support CAMS for HIS' is installed), B/M9000 CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R8.03.01). If an adjacent attacker successfully compromises a computer using CAMS for HIS software, they can use credentials from the compromised machine to access data from another machine using CAMS for HIS software. This can lead to a disabling of CAMS for HIS software functions on any affected machines, or information disclosure/alteration. | |||||
CVE-2022-27188 | 1 Yokogawa | 2 B\/m9000 Vp, Centum Vp | 2024-11-21 | 4.4 MEDIUM | 7.8 HIGH |
OS command injection vulnerability exists in CENTUM VP R4.01.00 to R4.03.00, CENTUM VP Small R4.01.00 to R4.03.00, CENTUM VP Basic R4.01.00 to R4.03.00, and B/M9000 VP R6.01.01 to R6.03.02, which may allow an attacker who can access the computer where the affected product is installed to execute an arbitrary OS command by altering a file generated using Graphic Builder. | |||||
CVE-2022-26034 | 1 Yokogawa | 2 B\/m9000 Vp, Centum Vp | 2024-11-21 | 5.8 MEDIUM | 9.1 CRITICAL |
Improper authentication vulnerability in the communication protocol provided by AD (Automation Design) server of CENTUM VP R6.01.10 to R6.09.00, CENTUM VP Small R6.01.10 to R6.09.00, CENTUM VP Basic R6.01.10 to R6.09.00, and B/M9000 VP R8.01.01 to R8.03.01 allows an attacker to use the functions provided by AD server. This may lead to leakage or tampering of data managed by AD server. | |||||
CVE-2022-23402 | 1 Yokogawa | 5 Centum Vp, Centum Vp Entry, Centum Vp Entry Firmware and 2 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
The following Yokogawa Electric products hard-code the password for CAMS server applications: CENTUM VP versions from R5.01.00 to R5.04.20 and versions from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00 | |||||
CVE-2022-23401 | 1 Yokogawa | 9 Centum Cs 3000, Centum Cs 3000 Entry, Centum Cs 3000 Entry Firmware and 6 more | 2024-11-21 | 3.7 LOW | 7.8 HIGH |
The following Yokogawa Electric products contain insecure DLL loading issues. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00. | |||||
CVE-2022-22729 | 1 Yokogawa | 9 Centum Cs 3000, Centum Cs 3000 Entry, Centum Cs 3000 Entry Firmware and 6 more | 2024-11-21 | 6.0 MEDIUM | 8.8 HIGH |
CAMS for HIS Server contained in the following Yokogawa Electric products improperly authenticate the receiving packets. The authentication may be bypassed via some crafted packets: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, and Exaopc versions from R3.72.00 to R3.79.00. | |||||
CVE-2022-22151 | 1 Yokogawa | 9 Centum Cs 3000, Centum Cs 3000 Entry, Centum Cs 3000 Entry Firmware and 6 more | 2024-11-21 | 4.9 MEDIUM | 8.1 HIGH |
CAMS for HIS Log Server contained in the following Yokogawa Electric products fails to properly neutralize log outputs: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, and Exaopc versions from R3.72.00 to R3.79.00. | |||||
CVE-2022-22148 | 1 Yokogawa | 9 Centum Cs 3000, Centum Cs 3000 Entry, Centum Cs 3000 Entry Firmware and 6 more | 2024-11-21 | 6.9 MEDIUM | 7.8 HIGH |
'Root Service' service implemented in the following Yokogawa Electric products creates some named pipe with improper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00. | |||||
CVE-2022-22145 | 1 Yokogawa | 9 Centum Cs 3000, Centum Cs 3000 Entry, Centum Cs 3000 Entry Firmware and 6 more | 2024-11-21 | 4.9 MEDIUM | 8.1 HIGH |
CAMS for HIS Log Server contained in the following Yokogawa Electric products is vulnerable to uncontrolled resource consumption. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00. | |||||
CVE-2022-22141 | 1 Yokogawa | 9 Centum Cs 3000, Centum Cs 3000 Entry, Centum Cs 3000 Entry Firmware and 6 more | 2024-11-21 | 4.4 MEDIUM | 7.8 HIGH |
'Long-term Data Archive Package' service implemented in the following Yokogawa Electric products creates some named pipe with imporper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00. | |||||
CVE-2022-21808 | 1 Yokogawa | 9 Centum Cs 3000, Centum Cs 3000 Entry, Centum Cs 3000 Entry Firmware and 6 more | 2024-11-21 | 6.0 MEDIUM | 8.8 HIGH |
Path traversal vulnerability exists in CAMS for HIS Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00. | |||||
CVE-2022-21194 | 1 Yokogawa | 5 Centum Vp, Centum Vp Entry, Centum Vp Entry Firmware and 2 more | 2024-11-21 | 6.8 MEDIUM | 9.8 CRITICAL |
The following Yokogawa Electric products do not change the passwords of the internal Windows accounts from the initial configuration: CENTUM VP versions from R5.01.00 to R5.04.20 and versions from R6.01.00 to R6.08.0, Exaopc versions from R3.72.00 to R3.79.00. | |||||
CVE-2022-21177 | 1 Yokogawa | 9 Centum Cs 3000, Centum Cs 3000 Entry, Centum Cs 3000 Entry Firmware and 6 more | 2024-11-21 | 4.9 MEDIUM | 8.1 HIGH |
There is a path traversal vulnerability in CAMS for HIS Log Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, andfrom R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00. | |||||
CVE-2020-5609 | 1 Yokogawa | 8 B\/m9000cs, B\/m9000cs Firmware, B\/m9000vp and 5 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
Directory traversal vulnerability in CAMS for HIS CENTUM CS 3000 (includes CENTUM CS 3000 Small) R3.08.10 to R3.09.50, CENTUM VP (includes CENTUM VP Small, Basic) R4.01.00 to R6.07.00, B/M9000CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R8.03.01 allows a remote unauthenticated attacker to create or overwrite arbitrary files and run arbitrary commands via unspecified vectors. | |||||
CVE-2020-5608 | 1 Yokogawa | 8 B\/m9000cs, B\/m9000cs Firmware, B\/m9000vp and 5 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
CAMS for HIS CENTUM CS 3000 (includes CENTUM CS 3000 Small) R3.08.10 to R3.09.50, CENTUM VP (includes CENTUM VP Small, Basic) R4.01.00 to R6.07.00, B/M9000CS R5.04.01 to R5.05.01, and B/M9000 VP R6.01.01 to R8.03.01 allows a remote unauthenticated attacker to bypass authentication and send altered communication packets via unspecified vectors. | |||||
CVE-2019-5909 | 1 Yokogawa | 4 B\/m 9000 Vp, Centum Vp, Prm and 1 more | 2024-11-21 | 10.0 HIGH | 9.8 CRITICAL |
License Manager Service of YOKOGAWA products (CENTUM VP (R5.01.00 - R6.06.00), CENTUM VP Entry Class (R5.01.00 - R6.06.00), ProSafe-RS (R3.01.00 - R4.04.00), PRM (R4.01.00 - R4.02.00), B/M9000 VP(R7.01.01 - R8.02.03)) allows remote attackers to bypass access restriction to send malicious files to the PC where License Manager Service runs via unspecified vectors. | |||||
CVE-2018-8838 | 1 Yokogawa | 5 B\/m9000 Cs, B\/m9000 Vp, Centum Cs 3000 and 2 more | 2024-11-21 | 4.4 MEDIUM | 6.5 MEDIUM |
A weakness in access controls in CENTUM CS 1000 all versions, CENTUM CS 3000 versions R3.09.50 and earlier, CENTUM CS 3000 Small versions R3.09.50 and earlier, CENTUM VP versions R6.03.10 and earlier, CENTUM VP Small versions R6.03.10 and earlier, CENTUM VP Basic versions R6.03.10 and earlier, Exaopc versions R3.75.00 and earlier, B/M9000 CS all versions, and B/M9000 VP versions R8.01.01 and earlier may allow a local attacker to exploit the message management function of the system. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:L/AC:H/PR:L/UI:N/S:U/C:L/I:H/A:H). | |||||
CVE-2018-16196 | 1 Yokogawa | 11 B\/m9000 Vp, Centum Cs 3000, Centum Cs 3000 Entry Class and 8 more | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
Multiple Yokogawa products that contain Vnet/IP Open Communication Driver (CENTUM CS 3000(R3.05.00 - R3.09.50), CENTUM CS 3000 Entry Class(R3.05.00 - R3.09.50), CENTUM VP(R4.01.00 - R6.03.10), CENTUM VP Entry Class(R4.01.00 - R6.03.10), Exaopc(R3.10.00 - R3.75.00), PRM(R2.06.00 - R3.31.00), ProSafe-RS(R1.02.00 - R4.02.00), FAST/TOOLS(R9.02.00 - R10.02.00), B/M9000 VP(R6.03.01 - R8.01.90)) allows remote attackers to cause a denial of service attack that may result in stopping Vnet/IP Open Communication Driver's communication via unspecified vectors. | |||||
CVE-2015-5628 | 1 Yokogawa | 29 B\/m9000 Vp, B\/m9000 Vp Firmware, B\/m9000cs and 26 more | 2024-11-21 | 10.0 HIGH | 9.8 CRITICAL |
Stack-based buffer overflow in Yokogawa CENTUM CS 1000 R3.08.70 and earlier, CENTUM CS 3000 R3.09.50 and earlier, CENTUM CS 3000 Entry R3.09.50 and earlier, CENTUM VP R5.04.20 and earlier, CENTUM VP Entry R5.04.20 and earlier, ProSafe-RS R3.02.10 and earlier, Exaopc R3.72.00 and earlier, Exaquantum R2.85.00 and earlier, Exaquantum/Batch R2.50.30 and earlier, Exapilot R3.96.10 and earlier, Exaplog R3.40.00 and earlier, Exasmoc R4.03.20 and earlier, Exarqe R4.03.20 and earlier, Field Wireless Device OPC Server R2.01.02 and earlier, PRM R3.12.00 and earlier, STARDOM VDS R7.30.01 and earlier, STARDOM OPC Server for Windows R3.40 and earlier, FAST/TOOLS R10.01 and earlier, B/M9000CS R5.05.01 and earlier, B/M9000 VP R7.03.04 and earlier, and FieldMate R1.01 or R1.02 allows remote attackers to execute arbitrary code via a crafted packet. |