Vulnerabilities (CVE)

Filtered by vendor Iconics Subscribe
Total 28 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2022-23128 2 Iconics, Mitsubishielectric 5 Analytix, Genesis64, Hyper Historian and 2 more 2024-02-28 7.5 HIGH 9.8 CRITICAL
Incomplete List of Disallowed Inputs vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.95.3 to 10.97, ICONICS Hyper Historian versions 10.95.3 to 10.97, ICONICS AnalytiX versions 10.95.3 to 10.97 and ICONICS MobileHMI versions 10.95.3 to 10.97 allows a remote unauthenticated attacker to bypass the authentication of MC Works64, GENESIS64, Hyper Historian, AnalytiX and MobileHMI, and gain unauthorized access to the products, by sending specially crafted WebSocket packets to FrameWorX server, one of the functions of the products.
CVE-2021-27040 3 Autodesk, Iconics, Mitsubishielectric 13 Advance Steel, Autocad, Autocad Architecture and 10 more 2024-02-28 4.3 MEDIUM 3.3 LOW
A maliciously crafted DWG file can be forced to read beyond allocated boundaries when parsing the DWG file. This vulnerability can be exploited to execute arbitrary code.
CVE-2021-27041 3 Autodesk, Iconics, Mitsubishielectric 13 Advance Steel, Autocad, Autocad Architecture and 10 more 2024-02-28 6.8 MEDIUM 7.8 HIGH
A maliciously crafted DWG file can be used to write beyond the allocated buffer while parsing DWG files. This vulnerability can be exploited to execute arbitrary code
CVE-2020-12011 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2024-02-28 7.5 HIGH 9.8 CRITICAL
A specially crafted communication packet sent to the affected systems could cause a denial-of-service condition or allow remote code execution. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; GenBroker32 version 9.5 and prior.
CVE-2020-12015 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2024-02-28 5.0 MEDIUM 7.5 HIGH
A specially crafted communication packet sent to the affected systems could cause a denial-of-service condition due to improper deserialization. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; ICONICS GenBroker32 version 9.5 and prior.
CVE-2020-12013 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2024-02-28 6.4 MEDIUM 9.1 CRITICAL
A specially crafted WCF client that interfaces to the may allow the execution of certain arbitrary SQL commands remotely. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 Version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server v10.96 and prior; ICONICS GenBroker32 v9.5 and prior.
CVE-2020-12009 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2024-02-28 5.0 MEDIUM 7.5 HIGH
A specially crafted communication packet sent to the affected device could cause a denial-of-service condition due to a deserialization vulnerability. This affects: Mitsubishi Electric MC Works64 Version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 Version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server v10.96 and prior; ICONICS GenBroker32 v9.5 and prior.
CVE-2020-12007 2 Iconics, Mitsubishielectric 11 Bizviz, Energy Analytix, Facility Analytix and 8 more 2024-02-28 7.5 HIGH 9.8 CRITICAL
A specially crafted communication packet sent to the affected devices could allow remote code execution and a denial-of-service condition due to a deserialization vulnerability. This issue affects: Mitsubishi Electric MC Works64 version 4.02C (10.95.208.31) and earlier, all versions; Mitsubishi Electric MC Works32 version 3.00A (9.50.255.02); ICONICS GenBroker64, Platform Services, Workbench, FrameWorX Server version 10.96 and prior; ICONICS GenBroker32 version 9.5 and prior.