A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
References
Configurations
Configuration 1 (hide)
AND |
|
History
21 Nov 2024, 07:35
Type | Values Removed | Values Added |
---|---|---|
References |
|
25 Sep 2024, 01:15
Type | Values Removed | Values Added |
---|---|---|
CWE | ||
References |
|
|
03 Aug 2023, 14:51
Type | Values Removed | Values Added |
---|---|---|
CPE | cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.2:*:*:*:*:*:*:* cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:* cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.1:*:*:*:*:*:*:* cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.3:*:*:*:*:*:*:* cpe:2.3:o:hitachienergy:rtu500_firmware:13.4.1:*:*:*:*:*:*:* |
|
First Time |
Hitachienergy
Hitachienergy rtu500 Hitachienergy rtu500 Firmware |
|
CWE | CWE-787 | |
CVSS |
v2 : v3 : |
v2 : unknown
v3 : 7.5 |
References | (MISC) https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch - Vendor Advisory |
26 Jul 2023, 06:15
Type | Values Removed | Values Added |
---|---|---|
New CVE |
Information
Published : 2023-07-26 06:15
Updated : 2024-11-21 07:35
NVD link : CVE-2022-4608
Mitre link : CVE-2022-4608
CVE.ORG link : CVE-2022-4608
JSON object : View
Products Affected
hitachienergy
- rtu500_firmware
- rtu500
CWE
CWE-787
Out-of-bounds Write