CVE-2022-2502

A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.
Configurations

Configuration 1 (hide)

AND
OR cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.1:*:*:*:*:*:*:*
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.2:*:*:*:*:*:*:*
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.3:*:*:*:*:*:*:*
cpe:2.3:o:hitachienergy:rtu500_firmware:13.4.1:*:*:*:*:*:*:*
cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*

History

21 Nov 2024, 07:01

Type Values Removed Values Added
References
  • () https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch -

25 Sep 2024, 01:15

Type Values Removed Values Added
CWE CWE-120
References
  • {'url': 'https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch', 'tags': ['Vendor Advisory'], 'source': 'cybersecurity@hitachienergy.com'}
  • () https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch -

03 Aug 2023, 19:26

Type Values Removed Values Added
CVSS v2 : unknown
v3 : unknown
v2 : unknown
v3 : 7.5
References (MISC) https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch - (MISC) https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch - Vendor Advisory
First Time Hitachienergy
Hitachienergy rtu500
Hitachienergy rtu500 Firmware
CWE CWE-20
CPE cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.2:*:*:*:*:*:*:*
cpe:2.3:h:hitachienergy:rtu500:-:*:*:*:*:*:*:*
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.1:*:*:*:*:*:*:*
cpe:2.3:o:hitachienergy:rtu500_firmware:13.3.3:*:*:*:*:*:*:*
cpe:2.3:o:hitachienergy:rtu500_firmware:13.4.1:*:*:*:*:*:*:*

26 Jul 2023, 06:15

Type Values Removed Values Added
New CVE

Information

Published : 2023-07-26 06:15

Updated : 2024-11-21 07:01


NVD link : CVE-2022-2502

Mitre link : CVE-2022-2502

CVE.ORG link : CVE-2022-2502


JSON object : View

Products Affected

hitachienergy

  • rtu500
  • rtu500_firmware
CWE
CWE-20

Improper Input Validation