A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP100 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP300 (All versions < V8.80). Received webpackets are not properly processed. An unauthenticated remote attacker with access to any of the Ethernet interfaces could send specially crafted packets to force a restart of the target device.
References
Link | Resource |
---|---|
https://cert-portal.siemens.com/productcert/pdf/ssa-500748.pdf | Patch Vendor Advisory |
https://cert-portal.siemens.com/productcert/pdf/ssa-500748.pdf | Patch Vendor Advisory |
Configurations
Configuration 1 (hide)
|
History
21 Nov 2024, 06:14
Type | Values Removed | Values Added |
---|---|---|
References | () https://cert-portal.siemens.com/productcert/pdf/ssa-500748.pdf - Patch, Vendor Advisory |
Information
Published : 2021-09-14 11:15
Updated : 2024-11-21 06:14
NVD link : CVE-2021-37206
Mitre link : CVE-2021-37206
CVE.ORG link : CVE-2021-37206
JSON object : View
Products Affected
siemens
- siprotec_5_with_cpu_variant_cp300
- siprotec_5_with_cpu_variant_cp050
- siprotec_5_with_cpu_variant_cp100
CWE
CWE-20
Improper Input Validation