CVE-2021-22659

Rockwell Automation MicroLogix 1400 Version 21.6 and below may allow a remote unauthenticated attacker to send a specially crafted Modbus packet allowing the attacker to retrieve or modify random values in the register. If successfully exploited, this may lead to a buffer overflow resulting in a denial-of-service condition. The FAULT LED will flash RED and communications may be lost. Recovery from denial-of-service condition requires the fault to be cleared by the user.
Configurations

Configuration 1 (hide)

AND
cpe:2.3:o:rockwellautomation:micrologix_1400_firmware:*:*:*:*:*:*:*:*
cpe:2.3:h:rockwellautomation:micrologix_1400:-:*:*:*:*:*:*:*

History

21 Nov 2024, 05:50

Type Values Removed Values Added
References () https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1129877/loc/en_US#__highlight - Permissions Required, Vendor Advisory () https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1129877/loc/en_US#__highlight - Permissions Required, Vendor Advisory
References () https://us-cert.cisa.gov/ics/advisories/icsa-21-033-01 - Third Party Advisory, US Government Resource () https://us-cert.cisa.gov/ics/advisories/icsa-21-033-01 - Third Party Advisory, US Government Resource

Information

Published : 2021-03-25 16:15

Updated : 2024-11-21 05:50


NVD link : CVE-2021-22659

Mitre link : CVE-2021-22659

CVE.ORG link : CVE-2021-22659


JSON object : View

Products Affected

rockwellautomation

  • micrologix_1400
  • micrologix_1400_firmware
CWE
CWE-120

Buffer Copy without Checking Size of Input ('Classic Buffer Overflow')