CVE-2020-28388

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.
Configurations

Configuration 1 (hide)

OR cpe:2.3:a:siemens:capital_vstar:*:*:*:*:*:*:*:*
cpe:2.3:a:siemens:nucleus_net:*:*:*:*:*:*:*:*
cpe:2.3:a:siemens:nucleus_source_code:*:*:*:*:*:*:*:*
cpe:2.3:a:siemens:pluscontrol_1st_gen:*:*:*:*:*:*:*:*

Configuration 2 (hide)

AND
cpe:2.3:a:siemens:nucleus_readystart:*:*:*:*:*:*:*:*
OR cpe:2.3:h:arm:arm:-:*:*:*:*:*:*:*
cpe:2.3:h:mips:mips:-:*:*:*:*:*:*:*
cpe:2.3:h:powerpc_project:powerpc:-:*:*:*:*:*:*:*

History

08 Aug 2023, 10:15

Type Values Removed Values Added
CWE CWE-342 NVD-CWE-Other
Summary A vulnerability has been identified in APOGEE PXC Series (BACnet) (All versions < V3.5.5), APOGEE PXC Series (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Series (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones. A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.
References
  • (MISC) https://cert-portal.siemens.com/productcert/pdf/ssa-180579.pdf -

Information

Published : 2021-02-09 18:15

Updated : 2024-02-28 18:08


NVD link : CVE-2020-28388

Mitre link : CVE-2020-28388

CVE.ORG link : CVE-2020-28388


JSON object : View

Products Affected

siemens

  • pluscontrol_1st_gen
  • capital_vstar
  • nucleus_source_code
  • nucleus_net
  • nucleus_readystart

arm

  • arm

mips

  • mips

powerpc_project

  • powerpc
CWE
NVD-CWE-Other CWE-342

Predictable Exact Value from Previous Values