An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability.Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0001 Fault Type: Non-User Description: A fault state can be triggered by setting the NVRAM/memory module user program mismatch bit (S2:9) when a memory module is NOT installed.
References
Link | Resource |
---|---|
https://www.talosintelligence.com/vulnerability_reports/TALOS-2017-0443 | Exploit Third Party Advisory |
https://www.talosintelligence.com/vulnerability_reports/TALOS-2017-0443 | Exploit Third Party Advisory |
Configurations
Configuration 1 (hide)
AND |
|
History
21 Nov 2024, 03:12
Type | Values Removed | Values Added |
---|---|---|
References | () https://www.talosintelligence.com/vulnerability_reports/TALOS-2017-0443 - Exploit, Third Party Advisory |
Information
Published : 2018-04-05 21:29
Updated : 2024-11-21 03:12
NVD link : CVE-2017-14464
Mitre link : CVE-2017-14464
CVE.ORG link : CVE-2017-14464
JSON object : View
Products Affected
rockwellautomation
- micrologix_1400
- micrologix_1400_b_firmware
CWE